Tap Changer

Bristo Power Engineers/Technicians have 10+ years of experience in L,V,D and M type OLTC and OCTC .

Tap Changer Diverter Switch Maintenance
Tap Changer Diverter Switch Withdrawal and Oil Compartment +
  • Drain the oil from the tap changer conservator and diverter switch oil compartment.
  • Dismount the drive shaft, if necessary.
  • Open the tap changer head cover.
  • Use suitable lifting tools or crane to withdraw the diverter switch from the oil compartment and place it on a clean workbench.
  • Clean the oil compartment thoroughly and remove all carbon sediments with appropriate materials & tools.
  • Check the insulation materials, fixed contacts, and other components of the oil compartment.
  • Align all the tap positions: Top, Motor, and RCC.
  • Change necessary O-rings, seals, and gaskets. Verify and check the selector switch contacts.
  • The service provider must arrange the necessary oil flange.
  • Confirm the condition of the insulating cylinder.
Tap Changer Diverter Switch Dismounting and Mounting +
  • Dismounting and mounting of the on-load tap-changer.
  • Remove the contact shells of the diverter switch.
  • Clean all components.
  • Check the transition resistor, measure the resistance value, and replace if required.
  • Check the flexible leads, contact carrier, and screw connections. Replace if required.
  • Install necessary inspection materials.
  • Carry out updating measures as recommended by the manufacturer.